Reference + lookup · 2 min read

ASHRAE W-classes (W17–W45)

ASHRAE sorts liquid-cooled equipment into coolant supply temperature classes: W17, W27, W32, W40, W45 — the number is the maximum facility water supply temperature in °C. Higher classes reject heat into warmer water, enabling chiller-free operation — if the IT hardware supports it.

The table

ClassMax facility supplyWhat it implies for the site
W17≈ 17 °CChilled water required — compressors run year-round; historic baseline
W27≈ 27 °CCooler climate or partial free cooling; chiller mostly shoulder-season
W32≈ 32 °CMost temperate sites' free-cooling target; dry coolers viable much of the year
W40≈ 40 °CChiller-less operation in most of Europe/North America via dry coolers
W45≈ 45 °CWarm-water direct-to-chip; the class behind "free cooling almost everywhere" claims — and the rating point of typical L2A cabinets
FIG. 1 — The class number ≈ maximum facility water supply temperature in °C. Quality, chemistry and wet-bulb limits apply on top — see notes.

Look up your site

Needs class ≥ 32
W32: the common free-cooling target — dry coolers cover much of the year in temperate sites

Reading it honestly

  • W-class is about the facility loop, not the room. Room air classes (A1-A4) are a separate ladder for air-cooled IT; do not mix them in a quote.
  • Warmer water trades chiller hours for chip margin. A W45 loop lets the site skip refrigeration, but every degree of warmer coolant raises cold-plate approach and chip temperatures — capacity and silicon limits pay for the efficiency.
  • Temperature is only half the spec. Classes assume water quality targets (corrosion, biology, particulates); PG25 with inhibitors is the usual answer on the technology loop (fluids).
  • Tropics cap the ladder. With design wet-bulbs near 28-30 °C, even W45 loops lose dry-cooler margin — the physics behind wet-bulb limits and SS 726.

Related

Wet-bulb & free cooling · Standards overview · Approach temperature · Glossary

Sources

ASHRAE liquid cooling guidance ("Water-Cooled Servers" framework, 2019) and the W-class family as cited in equipment datasheets. Class value ≈ max supply temperature; confirm exact envelope in the current ASHRAE edition and your vendor's spec.