Formula · 2 min read

PUE math — and what it hides

PUE = total facility energy ÷ IT energy: 100 kW of IT with 15 kW of overhead scores 1.15. Liquid cooling reaches 1.05-1.2 where air needs 1.4-1.6 — but the number assumes facility-scale infrastructure and honest climate, which single-cabinet deployments don't have.

Formula

PUE = (PIT + Pcooling + Ppower loss + Pmisc) / PIT

Worked example

(100 + 10 + 4 + 1) / 100 = 1.15

A facility moving 100 kW of IT heat with 10 kW of cooling energy (efficient free-cooling or liquid), 4 kW of UPS/conversion losses and 1 kW of lighting and controls runs at PUE 1.15. The same site on legacy air with 45 kW of cooling energy runs 1.50.

Try it

1.15
✅ 1.1-1.2 — good; typical for well-run liquid-cooled sites

What it hides

  • Climate is invisible. The same hardware scores differently in Munich and Singapore — free cooling hours depend on wet-bulb (wet-bulb physics). Cross-climate PUE comparisons are marketing, not engineering.
  • Liquid cooling doesn't shrink IT power. It shrinks the cooling term. A rack's IT draw is the same; what changes is how cheaply the heat leaves the building.
  • A cabinet in a room has no honest PUE. If the "facility" is office AC shared with humans, the boundary is undefined. Use the 1.1× room load rule instead for micro deployments.

Related

Room AC load · Wet-bulb & free cooling · Liquid vs air

Sources

Definition: The Green Grid / ISO/IEC 30134-2. Band context: Uptime Institute global surveys (air-cooled averages ≈ 1.5; leading liquid-cooled facilities 1.1 or below).