Liquid cooling, learned by moving numbers instead of reading paragraphs. Start with the loop below — then take a tool apart.

The loop, live

Servers → manifold → CDU → heat out. Drag anything; the flow speed, the heat arrows and the capacity verdict all follow.

COLD PLATESSERVER 1COLD PLATESSERVER 2COLD PLATESSERVER 340 kW IT · 75% TO LIQUIDMANIFOLDCDUPUMP · HX · CTRLHEAT OUT → ROOM AIR30.0 kW to removeAIR SHARE 10.0 kW cools by fans — the room AC still sees all 40 kW (1.1× rule)CAPACITY 50.0 kW · 60% USED · OK

flow 54 L/min (ΔT 8 °C) · liquid 30.0 kW · air 10.0 kW — same models as the flow, capture and derating pages

The tools

Why a playground

Models are first-order and anchored to published data where it exists (e.g. Vertiv XDU070 curves); they illustrate physics, not replace vendor engineering. If a tool says your room doesn't fit — that's the point: find out here, for free, before anyone ships anything.